Mã lỗi máy lạnh Haier

Trung tâm bh máy lạnh Haier xin gởi đến hành khách bảng mã lỗi của máy lạnh Haier, nếu hành khách đang dùng máy lạnh mang tên thương hiệu Haier nhưng gặp một trong những lỗi trên xin trực tiếp gọi đến TT Haier của Gia Khang để được bh sớm nhất .

Bảng mã lỗi máy lạnh Haier:

E01 flow switch fault

Troubleshooting:stop all module chillers

Bạn đang đọc: Mã lỗi máy lạnh Haier

Faliure resume : this fault is unresume failure
Must cut off power, after eliminate failures, then restart
E05 triple-phase AC input lack phase protection
Troubleshooting : stop all compressors 、 water pump 、 fan motor ( if master unit occurs this
fault, all modules will stop, slave unit occurs this fault, only corresponding module unit will stop ) ;
Troubleshooting resume : after AC input is normal, will auto resume ;
E06 triple-phase AC input phase sequence protection
Troubleshooting : stop all compressors 、 water pump 、 fan motor ( if master unit occurs this
fault, all module units will stop, if slave unit occurs this fault, only corresponding module unit will
stop ) ;
Failure resume : after power off, adjust phase sequence, will resume .
E07 water return sensor fault
Troubleshooting : stop all compressors 、 water pump ( if master unit occurs this fault, all
module units will stop, if slave unit occurs this fault, unit won’t do stop protection ) ;
Faliure resume : resume after change ambient sensor normally ;
E08 water outlet temp. sensor fault
Troubleshooting : stop this unit’s all compressors ;
Faliure resume : resume after change temp. sensor normally .
E09 outdoor ambient temp. sensor fault
Troubleshooting : stop this unit’s all compressors ;
Faliure resume : resume after change temp. sensor normally ;
E16 wired controller communication fault
Troubleshooting : system will do “ OFF ” manage
Faliure resume : auto resume after receiving wired controller communication signals .
E21 fan overload protection fault
Troubleshooting : stop this unit’s compressor
Faliure resume : unresumable
E22 A system high pressure protection
Troubleshooting : A system compressor stop ;
Faliure resume : resume after signals shut ;
E23 A system low pressure protection
Troubleshooting : A system compressor stops ;
Failure resume : resume after signals shut ;
E24 compressor 1 over current protection
Troubleshooting : A system compressor stops ;
Faliure resume : auto resume ;
E25 compressor 1 discharge temp. sensor open circuit or short circuit
Troubleshooting : A system compressor stops ;
Failure resume : auto resume after changing sensor normally ;
E26 A system coil ( outlet ) temp.sensor is open circuit or short circuit
Troubleshooting : stop A system compressor
Failure resume : auto resume after changing sensor .
E28 A system water exchange refigerant entrance port is open circuit or short circuit
Troubleshooting : stop A system compressor ;
Failure resume : auto resume after changing sensor normally ;
E29 A system suction temp. sensor is open circuit or short circuit
Troubleshooting : stop A system compressor
Failure resume : auto resume after changing sensor normally ;
E30 A system coil ( entrance ) temp. sensor is open circuit or short circuit
Troubleshooting : A system compressor stops ;
Failure resume : auto resume after changing sensor normally .
E31 compressor 1 discharge temp. sensor overhigh
Troubleshooting : A system compressor stops ;
Failure resume : resume after changing temp. sensor or discharging temp. sensor < 90 ℃
E32 A system coil ( exit ) temp.sensor temp. overhigh
Trooubleshooting : A system compressor stops ;
Failure resume : resume after A system coil ( exit ) senor temp. < 55 ℃ E39 compressor 2 overcurrent protection

Troubleshooting:A system compressor stops;

Failure resume : auto resume ;
E40 compressor 2 discharge temp. sensor is open circuit or short circuit
Troubleshooting : A system compressor stops ;
Failure resume : auto resume after change sensor normally ;
E46 compressor 2 discharge temp. is overhigh
Troubleshooting : A system compressor stops ;
resume : resume after compressor 2 discharge temp. < 90 ℃ E52 B system high pressure protection Troubleshooting : B system compressor stops ; Failure resume : auto resume after signals shut E53 B system low pressure protection Troubleshooting : B system compressor stops ; Failure resume : auto resume after signals shut ; E54 compressor 3 over current protection Troubleshooting : B system compressor stops ; resume : auto resume . E55 compressor 3 discharge temp. sensor is open circuit or short circuit ; Troubleshooting : Bsystem compressor stops ; Failure resume : auto resume ; E56 B system coil ( exit ) temp. sensor is short circuit or short circuit Troubleshooting : B system compressor stops ; Failure resume : auto resume after changing sensor normally . E57 B system water exchange refirgerant entrance temp.sensor is open circuit or short circuit Troubleshooting : B system compressor stops ; Failure resume : auto resume after changing sensor normally ; E58 B system water exchange refrigerant exit temp. sensor is open circuit or short circuit Troubleshooting : B system compressor stops ; Failure resume : auto resume after changing sensor normally . E59 B system suction temp. sensor is open circuit or short circuit Troubleshooting : B system compressor stops ; Failure resume : auto resume after changing sensor normally E60 B system coil ( entrance ) temp. sensor is open circuit or short circuit Troubleshooting : B system compressor stops ; Failure resume : auto resume after changing sensor normally ; E61 compressor 3 discharging temp. sensor overhigh Troubleshooting : B system compressor stops ; Failure resume : resume after changing temp. sensor or discharging temp. overhigh ; E62 B system coil ( exit ) temp. sensor overhigh Troubleshooting : B system compressor stops ; Failure resume : resume after B system coil ( exit ) sensor temp < 55 ℃ E69 compressor 4 overcurrent protection Troubleshooting : B system compressor stops ; Failure resume : auto resume ; E70 compressor 4 discharging temp. sensor is open circuit or short circuit Troubleshooting : B system compressor stops ; Failure resume : auto resume after changing sensor normally ; E76 compressor 4 discharging temp. sensor is overhigh Troubleshooting : B system compressor stops ; Failure resume : resume after changing temp. sensor or discharging temp. < 90 ℃

MỌI CHI TIẾT XIN LIÊN HỆ :

đường dây nóng : 0933 237 690

TRUNG TÂM ĐIỆN LẠNH GIA KHANG

VPĐD : Số 52, Đường D2, P.25 – Quận Bình Thạnh, TP.HCM

Trụ sở chính: Đường số 42, P. Tân Quý, Quận 7, TP.HCM

Trụ sở 1: 19A, Đường Quang Trung, Quận Gò Vấp, TP.HCM

Trụ sở 2: Số 143, Đường Ngô Quyền, Quận 5, TP.HCM

Trụ sở 3: 54, Đường Điện Biên Phủ, Phường 1, Quận 3, TP.HCM

Trụ sở 4: Số 143, Đường Lê Trọng Tấn, Quận Tân Phú, TP.HCM

Website: https://baoduongdieuhoa24h.com

E-Mail : [email protected]

Alternate Text Gọi ngay